Is clearance to an electrical panel required to the sides?

1

Did an inspection today. 600 Amps to this gigantic home.

Main panels did not meet the minimum clearances between.

One of the sub-panels had a 3-wire feed, with no metallic conduit between main and sub, and no 4th conductor. 120 and 240 volt circuits abound. Where's the ground. Neutral bar was isolated, BTW, so we've got THAT going for us

Inspection sticker proudly displayed.

What am I missing here?

Transformer on site. Water all around it. Conduit from transformer to inside of basement has water POURING from it, into 3'x3' distribution cabinet. BIG cables, and large metallic conductor bars. Meter is connected in parallel, and conduited outside.

Really dangerous situation with the water. Weep holes drilled in bottom of this cabinet for "drainage" Unfortunately, it drains directly onto two side-by-side disconnects to two more sub-panels elsewhere in the dwelling. Builder had electrical contractor try and fix problems. Dug trench at one...

0 0
2

I have a condo in a large building with many identical units. Several times other owners have mentioned that the original layout of the utility room isn't up to code due to the proximity of the water heater to the electrical panel--it comes up during sales inspections and some owners have spent quite a lot of money to relocate the panel.

In my research I haven't been able to find any such code; the nearest I can find is 110.26(A)(2) which dictates the free space around the panel.

NEC 110.26(A)(2) Width of Working Space.

The width of the working space in front of the electric equipment shall be the width of the equipment or 750 mm (30 in.), whichever is greater. In all cases, the work space shall permit at least a 90 degree opening of equipment doors or hinged panels.

By that standard the design is up to code, the water heater is just far enough to the side to provide the needed working space.

Is there another code that is specific to the...

0 0
3

The National Electric Code requires min. 3'0" there are several rules defined in section 110.26 of the NEC; for 600 volts or less it is:

left to right the minimum clearance is 30" or the width of the equipment, whichever is larger in height, there should be 6' 6'' minimum height to stand in front of the equipment (exception for dwelling units for panels 200 amps or less) the depth in front of the equipment varies depending on the voltage and surfaces of the opposite wall behind you: if the voltage is 150 volts to ground or less the depth of clearance is 30": as stated above; if the voltage is higher it depends of whether the opposite wall is insulated or not: if insulated the depth is 3' 6", if not insulated (such as cement block) the depth is 48"

I refer to these rules as the "refrigerator rule": the clearance in front of the equipment in question requires a dedicated clear space roughly the size of a large refrigerator

Was this answer useful?

...

0 0
4

Electrical panels not only have to meet the explicit measurement standards of OSHA and NFPA, they must also be reasonably considered "readily accessible." In a 2005 letter to the Marshall Space Flight Center, OSHA Director Richard Fairfax further clarified the term. If someone must use portable ladders, stools or chairs to reach the electrical equipment, it is not considered readily accessible. Climbing over or moving furniture and other impediments to reach the equipment also constitutes a violation of the "readily accessible" standard. If electrical panels are locked, they are still considered readily accessible, as long as qualified persons can quickly access the...

0 0
5

Are you protecting yourself from electric shock and burns? You're not if you fail to comply with the following three clearance requirements in Sec. 110-26 of the National Electrical Code (NEC): 1) at least a 3-ft clearance in front of all electrical equipment; 2) a 30 in.-wide working space in front of equipment operating at 600V or less; and 3) minimum headroom clearance of 6 ft or the height of the equipment, whichever is greater. Let's look at these three clearances in detail.

Depth of working space Sec. 110.26(a)(1)

The depth of the working space in front of exposed live parts must be at least as great as the distances outlined in Table 110-26(a). You must measure distances from live parts or from the front of the enclosure or opening in which the live parts are enclosed. The working clearance in front of the equipment on which you're working is also dependent on the composition of the facing wall and whether it houses live electrical parts. As...

0 0
6

how to calculate energy of 3-phase motor?

0 Answers Suzlon,

what are the safety measure & controls in engine?

2 Answers RRB,

What is Horan Gap Fuse? Where it is used?

1 Answers

A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N

0 Answers

What is difference between VCB and SF6 breaker

4 Answers

CAN ANY ONE EXPLAIN THE KNEE VOLTAGE OF THE CT?

3 Answers

HOW DO WE COLLECT THE SOLAR ENERGY AND DESCRIBE THE METHODS TO CONVERT THE SOLAR ENERGY INTO ELECTRICAL ENERGY?

1 Answers

at what basis/standard we have to arrive the current density of aluminium/ copper in busbar?

0 Answers ONGC,

3-PHASE 15KVA dg IS EQUIVALENT TO 12 KW,hOW?

2 Answers TATA,

I have 11KV/415V power distribution transformer. I have found unbalance current in LT (415V) side....

0 0
7

It depends what class the room is for one. Minimum of 1 meter around all sides of the panel is rule 2-308:

Working Space around electrical equipment:

(1.) A minimum working space of 1 m with secure footing shall be provided and maintained about electrical equipment such as switchboards, control panels, ans motor control centres that are enclosed in metal, except that working space is not required behind such equipment where there are no renewable parts such as fuses or switches on the back and where all connections are accessible from locations other than the back.

(2.)The space referred in Subrule (1) shall be in addition to the space required for the operation of draw-out-type equipment in either connected, test, or fully disconnected position and shall be sufficient for the opening of enclosure doors and hinged panels to at least 90 degrees.

(3.) Working space with secure footing not less than specified in table 56 shall be provided and maintained...

0 0
8

Alternating Current (AC)

The flow of electricity that constantly changes direction between positive and negative sides. Almost all power produced by electric utilities in the United States (and used by homes and business) is AC current that shifts direction at a rate of 60 times per second.

Ampere (Amp)

The unit of measure that indicates how much electricity flows through a conductor. It is like using cubic feet per second to measure the flow of water.

Amp-Hour Meter

This meter measures the cumulative energy going into or out of a system’s batteries, in order to provide an estimate of the state-of-charge.

Battery Box

A battery box may be a safety requirement for wet cell batteries and functions to contain hydrogen gas which is then vented to the outdoors. A battery box also protects the battery from the environment in outdoor remote or industrial applications.

Charge Controller

A charge...

0 0
9

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This article describes recessed light (downlight, pot light) clearance distances or spacing from insulation or wood or other combustibles in building ceilings, other indoor spaces or outdoors in roofs, soffits, porches.

This article series details guidelines for selecting and installing both exterior and interior lighting to meet the requirements for different building areas. Page top photo: this non-IC pot light improperly covered by insulation and contacting wood framing in this attic is a fire hazard.

Green links show where you are. © Copyright 2015 InspectApedia.com, All Rights Reserved.

Recessed Light Clearance Distances & Electrical Codes

What is the minimum clearance distance between the top of the recessed light can and wood framing or sheathing or insulation?

Reader question:

I am...

0 0
10

1969 Mustang Dynacorn Full Quarter Panel

The Full Quarter Panel from Dynacorn will fit 1969 Mustang fastbacks.

After years of use and abuse, the body panels in your 1969 Mustang fastback might be in need of repairs or replacement. With the Dynacorn Full Quarter Panel, you can get what you need and fully replace that body panel, helping to make your Mustang look like new again.

1. To begin installing your new Mustang Dynacorn 3645K Full Quarter Panel, make sure to measure everything! Make sure doors are on and close well with even lines along the old quarter. Measure from the front door jamb's top middle and bottom to the quarter panel. Measure the back window at the roof to the rear window's lower panel in three locations and draw it out on paper. Measure across rear window from quarter's edge to quarter edge in three locations. Measure the trunk lid's opening from both directions in three different locations. Measure locations of sail panel emblem...

0 0